Product Overview
The Potter PS40 Series Supervisory Pressure Actuated Switches are designed primarily to detect an increase and/or decrease from normal system pressure in automatic fire sprinkler systems. Typical applications are: Dry pipe systems, pre-action air/nitrogen supervision, pressure tanks, air supplies, and water supplies. The PS40 switch is factory set for 40 PSI (2,8 BAR) normal system pressure. The switch marked with the word LOW is set to operate at a pressure decrease of 10 PSI (,7 BAR) at 30 PSI (2,1 BAR). The switch marked with the word HIGH is set to operate at a pressure increase of 10 PSI (,7 BAR) at 50 PSI (3,5 BAR).
General Information
Name : Potter 1340408 PS402 High/Low Pressure Indicator , Potter Electric Signal, LLC
Category : Water Flow Controls
UPC Code :
Specifications
General Information
ADI Part Number : PL-1340408
Brand Name : Potter Electric Signal, LLC
Manufacturer : Potter Electric Signal, LLC
Manufacturer Part Number : 1340408
Product Name : Pressure Switch Canadian and Brass Connection
Product Type : Pressure Switch
Technical Information
Material : Nylon/Brass
Physical Characteristics
Depth : 3.20"
Height : 4.22"
Width : 3.78"