Product Overview
The Potter PS40 Series Supervisory Pressure Actuated Switches are designed primarily to detect an increase and/or decrease from normal system pressure in automatic fire sprinkler systems. Typical applications are: air/nitrogen supervision in dry pipe and pre-action systems, pressure tanks, air supplies, and water supplies. The PS40-1 has one switch and is factory set to activate at approximately 30 psi (2,1 bar) on a decrease
in pressure. The PS40-2 has two switches. The Low switch is factory set to activate at approximately 30 psi (2,1 bar) on a decrease in pressure. The High switch is factory set to activate at approximately 50 psi (3,5
bar) on an increase in pressure. NFPA 72 requires a supervisory signal if the pressure increases or decreases by 10 psi from normal. The PS40 is factory set for a normal air pressure of 40 psi. See section heading
Adjustments and Testing if other than factory set point is required.
General Information
Name : Potter 1340407 PS401 Low Pressure Indicator , Potter Electric Signal, LLC
Category : Water Flow Controls
UPC Code :
Specifications
General Information
ADI Part Number : PL-1340407
Brand Name : Potter Electric Signal, LLC
Manufacturer : Potter Electric Signal, LLC
Manufacturer Part Number : 1340407
Product Name : Pressure Switch Canadian and Brass Connection
Product Type : Pressure Switch